PIPA CASING : Casing pipes crossing under roadways/ railroads shall be located at suitable approved alignments in order to eliminate possible conflicts with existing or future utilities and structures, with a minimum 36-inch depth of cover between the top of the casing pipe and the surface of the roadway. Casing length shall extend a minimum of eight feet beyond the edge of pavement or curbing. Casings shall be pipe conforming to the requirements of ASTM Designation A-139. Carrier shall be Ductile Iron Pipe Class 250, HDPE C-905 or PVC C-900. The minimum casing pipe size and wall thickness shall be as shown in the following table for the water or wastewater carrier pipe size indicated. For sizes not included therein, or for special design considerations, approval shall be obtained from the Utilities Casing Pipe Size & Wall Thickness SIZE INCH THICKNESS INCH 12 " x Thickness 5/ 16 " 18 " x Thickness 5/ 16 " 20 " x Thickness 5/ 16 24 " x Thickness 3/ 8 " 24 " x Thickness 3/ 8 " 30 " x Thickness 1/ 2 " 42 " x Thickness 1/ 2 " 48 " x Thickness 1/ 2 " 54 " x Thickness 5/ 8 " 60 " x Thickness 5/ 8 " 66 " x Thickness 5/ 8 "