Detail PIPA CASING
PIPA CASING :
Casing pipes crossing under
roadways/ railroads shall be located at suitable
approved alignments in order to eliminate possible conflicts with existing or
future utilities and structures, with a minimum 36-inch depth of cover between the
top of the casing pipe and the surface of the roadway. Casing length shall extend
a minimum of eight feet beyond the edge of pavement or curbing. Casings shall
be pipe conforming to the requirements of ASTM Designation A-139. Carrier
shall be Ductile Iron Pipe Class 250, HDPE C-905 or PVC C-900. The minimum
casing pipe size and wall thickness shall be as shown in the following table for the
water or wastewater carrier pipe size indicated. For sizes not included therein, or
for special design considerations, approval shall be obtained from the Utilities
Casing Pipe Size & Wall Thickness
SIZE INCH THICKNESS INCH
12 " x Thickness 5/ 16 "
18 " x Thickness 5/ 16 "
20 " x Thickness 5/ 16
24 " x Thickness 3/ 8 "
24 " x Thickness 3/ 8 "
30 " x Thickness 1/ 2 "
42 " x Thickness 1/ 2 "
48 " x Thickness 1/ 2 "
54 " x Thickness 5/ 8 "
60 " x Thickness 5/ 8 "
66 " x Thickness 5/ 8 "